Guide On How To Test Motor Run Capacitors And Replace Them
Learn the steps required to properly test motor run capacitors on a farm. Before you start the test, you need to gather the tools you need to perform the capacitor test.
Electric multimeter with mode for continuity and capacitance
testing. Continuity is identified as the sound logo and amplitude is identified
by the capacitor logo (- || -) on the multimeter dial.
Capacitance meter to check the capacitance or operation of capacitors.
A set of multi-tool screwdrivers or sockets to open the
motor's condenser housing.
Insulated pliers to remove the spade connector from the
capacitor tab and retain the resistance to discharge.
An electrical resistor (15-20 kOhm) to dissipate the charge
of the capacitor. The electrician uses an electrically insulated screwdriver to
discharge the capacitor, which is not the recommended method.
Soldering iron (electric or gas pen) for removing and
reconnecting the bleed resistor, if connected to the starting capacitor.
The procedure for removing the condenser from the motor
Turn off
the power and make sure the engine you want to check (lockout-tagout) is
disconnected. The best way to make sure the power is off is to physically
disconnect the motor. However, they often have a waterproof switch that turns
the fan off. It is also recommended to cut the circuit breaker of the motor.
Find the
metal housing covering the starting and/or operating capacitors and remove it.
Use a
screwdriver or multi-tool socket to remove the screws on both sides of the
chassis.
After
removing the cover, replace the screws in their original positions so that they
do not get lost.
Before
removing, take a picture of the capacitor label, wire color and position.
Remove
the wire spade connector using insulating pliers, being careful not to touch the
terminals. Capacitors cannot be connected to the motor for an accurate reading.
Use a 20
kOhm resistor (or a screwdriver) to connect the terminals of the capacitor to
drain the charge. This should take up to a few seconds.
If the
bleeder resistor is soldered between the tabs of the starting capacitor, then
one leg of the resistor must be soldered from one tab to be able to measure the
capacitance.
This is
one of the most tedious steps in the process. Cutting the legs of the
resistance with pliers may seem faster, but good motor run capacitors will
make reconnection difficult.
Motor Capacitor Test
There
are four tests to assess whether the motor run capacitors are good or bad. Use the Motor Capacitor
Evaluation Worksheet at the end of this document to record the data collected
for each capacitor tested. You and your team can print these worksheets to
create a maintenance log for your farm.
Look for
signs of capacitors exploding. If there were signs of the capacitor exploding,
the relief port was eventually detonated. Or if the case is swollen, cracked,
or corroded, stop and replace the capacitor.
Test the
capacitor to make sure there is no electrical continuity inside the capacitor.
When
using a multimeter, turn the dial to the continuity label. There is usually a
sound wave symbol. Ensure that both ends of the multimeter are working by
bringing them in contact with each other. You will hear a beep.
Put two
leads on each of the reading terminals.
If you
hear a beep, this means that the capacitor is defective because it is carrying
current through the dielectric layer. Stop and replace the capacitor.
Test the
capacitor for short circuits between the capacitor material and the case.
Skip
this step if the capacitor housing is plastic.
When
using a multimeter, turn the dial to the continuity label. There is usually a
sound wave symbol. Ensure that both ends of the multimeter are working by
bringing them in contact with each other. You will hear a beep.
Place
one wire on the first tab and the second wire on the metal reading case. Repeat
to see the second tab on the metal case.
If you
hear a beep, this means that the capacitor is defective because it is passing
current from the insulator to the case. Stop and replace the capacitor.
Capacitor capacitance test
If you
are using an electrometer, convert the dial to the capacitance symbol (- || -).
It is difficult to get good readings from some capacitive multimeters, and some
multimeters may not have the ability to measure capacitance. You can use the
amplitude meter to complete this test.
To test
the capacitance, make sure the red and black leads are in place on the meter
(if the meter has multiple plug holes). If there are red leads, they must be
connected to the capacitance symbol.
Put two
leads on each terminal for reading.
Capacitance
measurements must be within the Microfarad (μF) rating on the label.
The
starting capacitor should be within ±20 percent of the listed capacitance.
The
operating capacitor should be within ±10 percent of the listed capacitance.
If the
reading is at or outside these limits, stop and replace the capacitor.
MOTOR
RUN CAPACITORS REPLACEMENT
If you
determine that the operating one of the motor
run capacitors is defective, you will need to replace the
damaged unit with a new one.
Record
label information for the test capacitor. Be sure to take a picture of the
capacitor label or enter the information into the motor capacitor assessment
worksheet.
The
capacitance ratings of the replacement capacitors must be the same.
Using a
lower capacitance (μF) is used in the starting capacitor, the same problem
occurs with the motor overheating as higher current is pushed through the
windings and can damage the motor.
If a
wrong capacitance is used for the operating capacitor, the magnetic field
around the motor will be erratic and the motor will resonate at full load. This
frequency makes the motor noisier, less efficient, and more susceptible to
overheating.
The
replacement capacitor shall have a voltage rating equal to or better than the
installed capacitor.
340V motor run capacitors can be used for 370V motor drive capacitors.
A370V
motor running capacitors cannot be used in place of 440V motor running
capacitors.
The
A370/440 V rating means that the same capacitor can be used for both voltages.
Replacement
capacitors should be similar in physical size. The new capacitor should fit
snugly into the chassis. Small diameters and lengths can cause capacitors to
slip and shorten housing tabs.
Name the
alternate capacitor. Label the replacement capacitors with a paint or marker
and tape (Fig. 13). This makes it easy to keep track of what has been tested
and replaced and to identify ongoing problems with this motor.
Safety Instructions
Always
disconnect electrical equipment prior to inspection and maintenance.
Always
consult an electrician when working with an electrical system.
By
design, kinetic capacitors store electrical energy. This energy is sufficient
to cause an electric shock to an individual and cause damage. Other injuries,
such as head injuries, may occur from falling backwards.
Always
read the manual and follow the technical and safety instructions when
performing maintenance work on the electrical system and its components.
Always
wear personal protective equipment (PPE).
If you like the article and would like to know more
please visit our website Amber Capacitors.

Comments
Post a Comment